§ 42-66. Backflow protection where minimum air gap cannot be provided.  


Latest version.
  • Devices to protect against backpressure and backsiphonage shall be installed at all fixtures and equipment where backflow may occur and where a minimum air gap cannot be provided between the water outlet to the fixture or equipment and its flood-level rim. For connections not subject to backpressure, a pressure vacuum breaker may be installed in the supply line or an atmospheric vacuum breaker shall be installed on the discharge side of the last valve on the line serving the fixture or equipment. For connections subject to backpressure, a reduced pressure principle backflow preventer or a double check valve assembly shall be installed on the line serving the fixture or equipment.